VIPA System SLIO
Approach transfer via MPI
interface
4.9.2 Transfer via Ethernet
Initialization
Transfer
4.9.3 Transfer via memory card
Proceeding transfer via
memory card
HB300 | CPU | 013-CCF0R00 | en | 16-40
1.
Connect your PC to the MPI jack of your CPU via a MPI programming cable.
2.
Load your project in the SIMATIC Manager from Siemens.
3.
Choose in the menu 'Options è Set PG/PC interface'.
4.
Select in the according list the "PC Adapter (MPI)"; if appropriate you have to add it
first, then click on [Properties].
5.
Set in the register MPI the transfer parameters of your MPI net and type a valid
address.
6.
Switch to the register Local connection.
7.
Set the COM port of the PCs and the transfer rate 38400baud for the MPI program-
ming cable from VIPA.
8.
Transfer your project via 'PLC è Load to module' via MPI to the CPU and save it
with 'PLC è Copy RAM to ROM' on a memory card if one is plugged.
So that you may access the according Ethernet interface you have to assign IP address
parameters by means of the "initialization".
X1/X2: Ethernet PG/OP channel
n
Ä Chapter 4.6 'Hardware configuration - Ethernet PG/OP channel' on page 64
–
1.
For the transfer, connect, if not already done, the appropriate Ethernet port to your
Ethernet.
2.
Open your project with the Siemens SIMATIC Manager.
Set via 'Options è Set PG/PC Interface' the access path to "TCP/IP ® Network
3.
card .... ".
Click to 'PLC è Download' Download ® the dialog "Select target module" is
4.
opened. Select your target module and enter the IP address parameters of the
Ethernet PG/OP channel for connection. Provided that no new hardware configura-
tion is transferred to the CPU, the entered Ethernet connection is permanently
stored in the project as transfer channel.
5.
With [OK] the transfer is started.
System dependent you get a message that the projected system differs
from target system. This message may be accepted by [OK].
® Your project is transferred and may be executed in the CPU after
transfer.
The memory card serves as external storage medium. There may be stored several proj-
ects and sub-directories on a memory card. Please regard that your current project is
stored in the root directory and has one of the following file names:
n
S7PROG.WLD
n
AUTOLOAD.WLD
1.
Start the Siemens SIMATIC Manager with your project
2.
Create with 'File è Memory Card File è New' a new wld file.
Deployment CPU 013-CCF0R00
Project transfer > Transfer via memory card
73