Deployment CPU 013-CCF0R00
Project transfer > Transfer via MPI

4.9 Project transfer

Overview

4.9.1 Transfer via MPI

General
Net structure
MPI programming cable
Terminating resistor
72
There are the following possibilities for project transfer into the CPU:
n
Transfer via MPI
n
Transfer via Ethernet
n
Transfer via memory card
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
ment storage media - VSD, VSC' on page 83
For transfer via MPI the CPU has the following interface:
Ä 'X3: MPI(PtP) interface' on page 39
The structure of a MPI net is electrically identical with the structure of a PROFIBUS net.
This means the same rules are valid and you use the same components for the build-up.
The single participants are connected with each other via bus interface plugs and
PROFIBUS cables. Per default the MPI net runs with 187.5kbaud. VIPA CPUs are deliv-
ered with MPI address 2.
The MPI programming cables are available at VIPA in different variants. The cables pro-
vide a RS232 res. USB plug for the PC and a bus enabled RS485 plug for the CPU. Due
to the RS485 connection you may plug the MPI programming cables directly to an
already plugged plug on the RS485 jack. Every bus participant identifies itself at the bus
with an unique address, in the course of the address 0 is reserved for programming
devices.
A cable has to be terminated with its surge impedance. For this you switch on the termi-
nating resistor at the first and the last participant of a network or a segment. Please make
sure that the participants with the activated terminating resistors are always power sup-
plied. Otherwise it may cause interferences on the bus.