Modbus Device Settings - YASKAWA ENC-G5 Quick Manual

Table of Contents

Advertisement

Modbus Device Settings

FA1-7012123000203
-> Refresh :
2022-09-16 10:30:32 GMT -6
Model :
FA1-C
SN :
7012123000203
Firmware :
1.2200
Server :
mqtt.solectria.com 1884
Status :
Online
Internet :
Ethernet
Ethernet Status :
Connected
Baud Rate :
9600 N8 1
Modbus ID :
1 - 10
Device Settings
Internet Settings
Settings
Baud Rate
9600 N 8 1
Modbus ID Range
Gateway Mode
GW-FOM
Raw Data Forward
Modbus TCP
Upgrade Firmware
Reboot
Reset
The gateway is config-
ured with a default
modbus ID range. Click
on "Device settings".
The gateway will scan
the daisy chain and list
the device list with the
default IDs.
The user can either
rescan the target IDs
individually in the list,
or scan the daisy chain
in full.
By clicking "More", the
user can edit the
Refresh
modbus ID range.
More
None
Page 24
Daisy Chain Info
ID: 1
Scan
Model: not scanned
Status:
ID: 2
Scan
Model: not scanned
Status:
ID: 3
Scan
Model: not scanned
Status:
ID: 4
Scan
Model: not scanned
Status:
ID: 5
Scan
Model: not scanned
Status:
Scan the whole daisy chain
Modbus ID Range
Supports the discontinuous ID in the range of 1 - 246.
Modbus ID 165, 222, 253, 254 should not be used.
1 - 5 :
PVI25KTL-DO/US-480 [SOL]
Add new device ID
Enter
Enter
Enter
Enter
Enter
Save