12
CONCEPT OF MULTIPLE CPU SYSTEM
(2) When CPU No.1 is the Q06CCPU-V(-B)
12
- 6
12.1 Mounting Positions of CPU Modules
The positions of respective CPU modules are shown in Table 12.6.
(a) Mounting position of a C Controller module
Up to four C Controller modules can be mounted on the CPU slot (the slot on the
right of the power supply module) and Slot 0 to Slot 2 of the main base unit.
(b) Mounting position of a Motion CPU
1) Up to three Motion CPUs (except the Q172DCPU and Q173DCPU) can be
mounted on Slot 0 to Slot 2
2) No Motion CPU can be used when the main base unit is the Q3 SB or
Q3 DB.
(c) "CPU (Empty)" setting
For details, refer to the following section.
Page 12-2, Section 12.1 (1) (c)