16
TROUBLESHOOTING
(2) Corrective actions
(b) For the Q06CCPU-V(-B)
1) When downloading a user program to a C Controller module
Error: This is not an elf module for the SH architecture.
Error: Object module load failed for C:/xxx/Demo1.out
Removed Demo1.out
WTX Error 0x1002e (LOADER_UNKNOWN_OBJ_MODULE_FORMAT)
2) When executing a user program with the ld command
ld(1,0,"/ROM/Demo1.out")
Incorrect ELF header size: 13312
ld error: error reading file (errno = 0x3d0001).
value = 0 = 0x0
1) Check the endian format of the user program.
For the checking method, refer to the following.
C Controller Module User's Manual (Utility Operation, Programming)
2) If the endian format of the user program is different from that of the C
Controller module, recompile the user program so that the same endian format
will be used.
16.2.14 When an error occurred during user program download or ld command execution
from target..........done
Figure 16.16 Error message
Figure 16.17 Error message
16.2 Troubleshooting