Output (Y) Status Setting For Switching From Stop To Run; Previous State (Default); Reset Output (Y) - Mitsubishi Electric Q12DCCPU-V User Manual

Melsec q series, c controller module
Hide thumbs Also See for Q12DCCPU-V:
Table of Contents

Advertisement

4
FUNCTIONS
(3) Processing

(4) Output (Y) status setting for switching from STOP to RUN

4
- 27
4.6 Output (Y) Status Setting for Switching STOP to RUN
(a) Previous state (Default)
The output status (Y) immediately before the change to STOP is output.
Then, output from the user program is enabled.
(b) Reset output (Y)
The outputs turn to OFF.
Then, output from the user program is enabled.
For forcing the output (Y) to turn ON in the STOP status, refer to the following.
(5) in this section
STOP
Output the
output status (Y)
before STOP?
Outputs the output status (Y)
immediately before entering
the STOP status.
Enables output (Y) from
the user program.
Figure 4.8 Output (Y) processing when the status is changed from STOP to RUN
In <<System settings>> of C Controller setting utility, the output status after switching
from STOP to RUN can be selected in advance.
Output mode
setting for
switching from
STOP to RUN
Figure 4.9 Output mode setting for switching STOP to RUN
RUN
NO (Reset output (Y))
YES (Previous state (default))