(2) Input response time setting

1) Configure I/O assignment settings.
(3) Precautions
4
- 35
4.8 Input Response Time Selection (I/O Response Time)
The input response time is set in "I/O assignment" in <<I/O assignment settings>> of
C Controller setting utility.
1) Configure the I/O assignment settings.
Detailed settings
2) Select
3) Set each input response time in the "I/O module, Intelligent function module
detailed settings" window.
2) Click the Detailed settings button.
Figure 4.12 Input response time setting
(a) When the input response time is reduced
Reducing the input response time value for high-speed response will make the
module noise-sensitive.
Take into account the operating environment when setting the input response
time.
(b) Timing when the setting takes effect
The input response time setting takes effect when:
• The C Controller system is powered on, or
• The C Controller module is reset.
.
3) Select an input response time.