2
SYSTEM CONFIGURATION
(2) For the Q06CCPU-V(-B)
2
- 8
2.1 System Configuration
2.1.3 Connection with peripheral devices
C Controller module
Target devices (such as personal computer and C Controller
module)
GOT, RS-232 cable (sold separately)
Figure 2.7 Connection with peripheral devices
* 1 Q06CCPU-V does not support the IEEE802.3x flow control.
Therefore, when the load of an Ethernet line is high in the connection with the hub supporting
IEEE802.3x, the data to be sent to the module may be lost.
If the above mentioned phenomenon occurs, add the hubs and reduce the load on the Ethernet
line applied on single hub.
Hub (sold separately)*1
Twisted pair cable
(Straight cable)
(sold separately)