Ph# Service

Default:
Blank
Selection:
Blank, P, B, or D
See the introduction to Phone Routing for a
description of the selections.
1.3

Power Supervision

AC Fail Time

Default:
10
Selection:
1 to 90 sec. (Blank and 0 are invalid)
Amount of time (in seconds) that AC power must be
off before the D9112 responds to the AC failure.
The response to restoral of AC power is delayed for
the same amount of time. The panel always monitors
AC. To disable audible and reporting failure
responses, program the following items NO:
Fail/Res Rpt

AC Tag Along

,
Buzz
.
0101
Visual AC Failure Response: When a
0101
failure occurs, the SERVC AC FAIL
0101
message displays at command centers.
You can program other AC failure
responses in the program items that follow,
and you can program a relay to activate in
Relay Parameters.

AC Fail/Res Rpt

AC Power Supervision
central station when they occur. To comply with UL
864 requirements for Commercial Fire Systems,
AC Fail/RES Rpt
program
Default:
No
Selection:
Yes or No
AC Failure
Yes
are sent to the central station when the
panel generates the event. They are
routed to the telephone number for
Power/Phone
reported as Trouble Zone 0 when
transmitting in BFSK.
AC Failure
No
are NOT sent when they occur. They
can still be sent with subsequent
reports if
programmed YES.
Bosch Security Systems | 2/04 | 74-06145-000-D
Panel Wide Parameter
AC
AC/Battery
, and
reports are sent to the
NO.
AC Restoral
and
reports
events. AC Failure is
AC Restoral
and
reports
AC Tag Along
is
AC Tag Along
AC Failure
Send
(tag along) with other reports. To comply with UL
864 requirements for Commercial Fire Systems,
AC Tag Along
program
Default:
Selection:
Yes
,
No

AC/Battery Buzz

Turn the command center trouble buzzer on when
AC fails or the battery is low or missing. This
program item does not prevent the SERVC AC
FAIL or SERVC BATT LOW displays.
Default:
Selection:
Yes
No
report as an additional message
YES.
No
Yes or No
When AC fails, the report is not sent
until another event occurs. The
Fail
report is sent to the receiver with
subsequent event reports until the
Restoral
report is sent. These
reports are routed to the phone
destination of the event with which it is
sent. If AC power restores before any
other event occurs, the report is not
sent.
Note:
AC Fail/Res Rpt
If both
Tag Along
are YES, two
Failure
reports are sent to the
Power/Phone
telephone number(s),
once as the primary message, and once
as the "tag along" report.
AC Fail
reports are not tag along
events.
No
Yes or No
Buzz command center sounder when
AC fails or the battery is low or missing.
To comply with NFPA standards for fire
systems, program this item YES.
Do not audibly indicate AC failure or
battery trouble on the command center.