en | On-board points
Callout - Description
2 - Normally closed device (contact)
3 - 1.0 kΩ resistor at device
4 - 1.0 kΩ resistor at EOL (end-of-line)
12.2

Point response time

The control panel scans on-board and off-board point sensor loops every 410 milliseconds.
The Debounce parameter in the Point Assignment section of RPS determines point response
time by setting the length of time the control panel scans a point before initiating an alarm.
The debounce time can range from 410 milliseconds to 6.15 seconds. The default for
Debounce is 820 ms.
Notice!
Increasing Debounce time might cause missed alarms. If you increase the Debounce time,
detection devices can enter alarm and reset without exceeding the point response time.
Leave Debounce at the default of 820 ms for all points except for:
Debounce does not apply to points with Point Source configured as Wireless, Output, or IP
Camera.
2016.06 | 08 | F.01U.303.996
points assigned to a Point Index with the Point Type set to Interior Follower, and the
point Source parameter set to ZONEX. Set Debounce to 1.23 s for these points.
points with the point Source parameter set to Door, and the access control module (B901
or D9210C) set to an SDI address. Set Debounce to 1.64 s for these points.
Installation and System Reference Guide
Control Panels
Bosch Security Systems, Inc.