Point Response Time; Wiring Information For Installations Using The - Bosch D9412G Operations & Installation Manual

Table of Contents

Advertisement

D9412G/D7412G | Operation & Installation Guide |
7.4

Point Response Time

The panel scans both on-board and off-board point
sensor loops every 300 milliseconds. The Debounce
Count program item in the
determines point response time by setting the number of
scans that a point must be faulted before the panel
initiates an alarm.
The debounce count can range from 2 to 15; therefore,
point response time ranges from 600 milliseconds to 4.5
seconds. The Bosch Security Systems default for
debounce count is 2.
Increasing debounce may cause missed
alarms.
If you increase the debounce count,
detection devices may go into alarm and
reset without exceeding the point response
time.
Bosch Security Systems recommends a debounce count
of 2 for all points except for Interior Follower points,
which should be programmed as a 3. In addition, door
points connected to a D9210B Access Control Interface
Module should be programmed with a debounce of 4.
Bosch Security Systems | 10/03 | 43488E
7.0 On-Board Points
Point Assignment
section
7.5
Wiring Information for Installations
Using the Ademco AB-12
Bell/Housing
1. Disconnect the wire jumper from Terminal 4 to the
inner housing of the Bell Box to prevent a ground
fault condition.
2. Connect wiring between the control and Bell Box as
shown in Figure 13.
To use the AB-12 Bell/Housing, place the S3 switch
in the disabled (open) position. The EOL used in the
AB-12 Bell/Housing must be a 220 kΩ, 0.5 W
resistor.
3. Program Point 8 as 24-hour, ALARM on open and
short. (PT TYPE 0, PT RESPONSE 0).
EN | 34

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412g

Table of Contents