56
en | On-board points
Callout - Description
2 - Normally closed device (contact)
3 - 1.0 kΩ resistor at device
4 - 1.0 kΩ resistor at EOL (end-of-line)
12.2
Point response time
The control panel scans on-board and off-board point sensor loops every 250 milliseconds.
The Debounce parameter in the Point Assignment section of RPS determines point response
time by setting the length of time the control panel scans a point before initiating an alarm.
The debounce time can range from 250 milliseconds to 6.15 seconds. The default for
Debounce is 820 ms.
Notice!
Increasing Debounce time might cause missed alarms. If you increase the Debounce time,
detection devices can enter alarm and reset without exceeding the point response time.
Debounce does not apply to points with Point Source configured as Wireless, Output, or IP
Camera.
2017.04 | 15 | F.01U.287.180
Installation Manual
Control Panels
Bosch Security Systems, Inc.