A# Fire Pat; A# Burg Time; A# Burg Pat - Bosch D9112B Program Entry Manual

Control panel
Table of Contents

Advertisement

D9112B | Program Entry Guide | 2.0

A# Fire Pat

Select the bell pattern this area uses to signal an alarm on a fire point.
Press the [SPACE] bar to scroll through the selections. Press [ENT] when the correct selection appears in the
display.
Default:
Pulse
Selection:
Steady, Pulse, CaStnd, TmCod3
Steady
Steady output
Pulse
Pulse March Time: 120 beats per minute at an even tempo
CaStnd
California Standard: 10 sec. audible + 5 sec. silent + 10 sec. audible + 5 sec. silent.
Note:
This sequence repeats until bell time expires.
TmCod3
Temporal Code 3: 0.5 to 1.0 sec. audible + 0.5 sec. silent + 0.5 sec. to 1.0 sec. audible + 0.5 sec. silent
+ 0.5 sec. to 1.0 sec. audible + 2.5 sec. silent.
Note:
This sequence repeats for a minimum of three min. with
allow automatic silencing as permitted by the AHJ, and carry a minimum ring time of five min.).

A# Burg Time

Default:
6
Selection:
1 to 90
Enter the number of minutes the bell rings for non-
fire alarm points.
The bell output begins as soon as the alarm occurs.
When the panel's internal clock begins a new
minute, it considers the first minute expired. It ends
the timing and shuts off the bell when the
programmed number of minutes expires.
If a passcode is entered to silence the bell before the
Cancel
time expires, and
Cancel
YES in Phone, a
to the same phone that the alarm message is routed
to.
The output for the alarm bell is determined by
programming in the Relays section of the program.
Relay A is the programmed default providing non-
fire alarm bell output for all eight areas. Relay A is
the D9112's on-board relay providing powered
alarm output from terminal 6. An optional D136
Relay can be installed on the D9112 to provide
powered alarm output from terminal 7 (known as
relay "B").
Bosch Security Systems | 2/04 | 74-06145-000-D
Area Wide Parameters
report is programmed
report is generated and sent
25% timing tolerance (1991 NFPA standards
Because the relay number is programmable by area,
you may change the relay number to provide
separate alarm outputs for each area. The relay
assigned provides bell output for the number of
Burg Time
minutes specified in
Burg Pat
pattern set in
.
Summary Alarm
A
relay is also available in the
Relays section of the program. It does not follow bell
pattern or time.

A# Burg Pat

Default:
Steady
Selection:
Steady, Pulse, CaStnd, TmCod3
Select the bell pattern this area uses to signal an
alarm on a non-fire point.
Fire Pat
See
for a description of each selection.
Press the [SPACE] bar to scroll through the
selections. Press [ENT] when the correct selection
appears in the display.