Fire Monitoring Communication Systems; Programming; Protecting The Control Panel – Burglary - Bosch B9512G Installation Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

8
en | ULC Installation Guide

Fire Monitoring Communication Systems

Refer to Wiring, page 15. The central station receiver must
receive fire alarms in 60 seconds and trouble signals in 90
seconds.
Type
Transmitters and supervision
Passive
1
Active
2
1
Test the transmission on each communication channel every 24 hours.
2
Check-in/polling signal required every 90 seconds.
To monitor a complete fire system, each ULC labeled intrusion system
must be connected to a ULC labeled fire alarm control panel. The system
must transmit system fire alarms, and supervisory and troubles signals to
the central station receiver.

Programming

You must follow the notes in the installation and programming
sections describing the system configurations for ULC Listed
installations.
Protecting the control panel – Burglary
The local control panel and local power supply must be
protected in one of the following ways:
2019.06 | 02 | F.01U.321.698
For transmitters at the protected premises
and supervision of communication
channels, refer to the figures in Fire
monitoring communication systems wiring
diagrams, page 18.
The control panel and power supply must be located within
the area of greatest protection on a tamper protected
circuit.
When arming, each area must arm the area that is
protecting the control panel and any external power supply
running an audible device. This might require duplicate
protection armed by each area. Access to this protected
area, without causing an alarm, requires that all areas are
disarmed.
Control Panels
Receivers
D6600 or
D6100IPv6
Bosch Security Systems B.V.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents