7.2.4

Precautions on power supply capacity

Select a power supply having enough power for a power supply module. (For an AC power supply module, the power
capacity should be twice or more as great as the current consumption of the power supply module, and four times or
more for a DC power supply module.)
(1) When the Q64RP or Q64P is used
The Q64RP and Q64P automatically recognize the rated input voltage waveform to switch the input voltage
between 100VAC and 200VAC.
If the power supply of insufficient power capacity is selected, the power supply module might fail when 200VAC
power is supplied.