Error
Error and cause
code
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
2114
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
2115
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic timing
• When instruction executed/STOP  RUN
[SP. UNIT ERROR]
• An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
• Instruction was executed for the A or QnA
2116
module under control of another CPU.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
[SP. UNIT ERROR]
A CPU module that cannot be specified in the
instruction dedicated to the multiple CPU system
was specified.
2117
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
[SP. UNIT ERROR]
When the online module change setting is set to
be "enabled" in the PLC parameter in a multiple
CPU system, intelligent function module controlled
by other CPU using the FROM
instruction/intelligent function module device
2118
(U\G) is specified.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
338
Corrective action
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
• When performing the online module
change in a multiple CPU system, correct
the program so that access will not be
made to the intelligent function module
controlled by the other CPU.
• When accessing the intelligent function
module controlled by the other CPU in a
multiple CPU system, set the online
module change setting to be "disabled" by
parameter.
LED status,
Corresponding
CPU status
RUN: Off/On
Q00J/Q00/Q01
ERR.:Flashing/On
Qn(H)
QnPH
CPU Status:
Stop/Continue
RUN: Off/On
ERR.:Flashing/On
Q00J/Q00/Q01
Qn(H)
CPU Status:
QnPH
Stop/Continue
RUN: Off/On
Q00J/Q00/Q01
ERR.:Flashing/On
Qn(H)
QnPH
CPU Status:
Stop/Continue
RUN: Off/On
Q00J/Q00/Q01
ERR.:Flashing/On
Qn(H)
QnPH
CPU Status:
Stop/Continue
RUN: Off/On
ERR.:Flashing/On
Qn(H)
QnPH
CPU Status:
Stop/Continue
CPU
QnU
QnU
QnU
QnU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents