Mitsubishi Electric Q26UD(E)HCPU User Manual page 337

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[SP.UNIT LAY ERR.]
• Five or more MELSECNET/H modules have
been installed.
• Five or more Ethernet interface modules have
been installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
• Two or more MELSECNET/H modules were
installed.
• Two or more Ethernet modules were installed.
• Three or more CC-Link modules were installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
2106
The same network number or same station
number is duplicated in the MELSECNET/H
network system.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
Two or more Ethernet modules were installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
Three or more Ethernet modules were installed.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[SP.UNIT LAY ERR.]
The start X/Y configured in the I/O Assignment tab
of "PLC Parameter" is overlapped with that for
another module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
2107
[SP.UNIT LAY ERR.]
The start X/Y configured in the I/O Assignment tab
of "PLC Parameter" is overlapped with that for
another module.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Corrective action
• Reduce the number of MELSECNET/H
modules to four or less.
• Reduce the number of Ethernet modules to
four or less.
• Mount only one MELSECNET/H module.
• Mount only one Ethernet module.
• Reduce the number of CC-Link modules to
two or less.
Check the network number and station
number.
Mount only one Ethernet module.
Reduce the number of Ethernet modules to
two or less.
Configure the I/O assignment setting of the
PLC parameter again so that it is consistent
with the actual status of the intelligent
function modules, special function modules,
and I/O modules.
• Configure the start X/Y again in the I/O
Assignment tab of "PLC Parameter"
according to the intelligent function module
and I/O modules connected.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
APPENDICES
LED status,
Corresponding
CPU status
CPU
Qn(H)
QnPH
QnPRH
Q00J/Q00/Q01
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
L02SCPU
L02SCPU-P
L02CPU
L02CPU-P
L06CPU
L06CPU-P
L26CPU
L26CPU-P
L26CPU-BT
L26CPU-PBT
QCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
A
335