(2) Regulations regarding immunity
Standard
EN61000-4-2
Electrostatic discharge
immunity
EN61000-4-3
Radiated,
radio-frequency,
electromagnetic field
immunity
EN61000-4-4
Electrical fast
transient/burst immunity
EN61000-4-5
EN61131-2:
Surge immunity
2007
EN61000-4-6
Immunity to conducted
disturbances, induced by
radio-frequency fields
EN61000-4-8
Power-frequency
magnetic field immunity
EN61000-4-11
Voltage dips and
interruption immunity
*1:
Programmable controllers are open-type devices (devices designed to be housed inside other equipment) and must be
installed inside a conductive control panel. The corresponding tests were conducted with the programmable controller
installed inside a control panel.
*2
The accuracy of an analog-digital converter module may temporary vary within ±10%.
Test item
Test description
Immunity test in which
electrostatic is applied to the
*1
cabinet of the equipment.
Immunity test in which electric
fields are irradiated to the
product.
*1
Immunity test in which burst
noise is applied to the power
*1
line and signal line.
Immunity test in which
lightning surge is applied to
*1
the power line and signal line.
Immunity test in which high
frequency noise is applied to
the power line and signal line
*1
Immunity test in which the
product is installed in
*1
inductive magnetic field
Immunity test in which power
supply voltage is momentarily
*1
interrupted
APPENDICES
Value specified in standard
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power,
AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 1kV
• AC power line, AC I/O power,
AC I/O (unshielded):
2kV CM, 1kV DM
• DC power line, DC I/O power:
0.5kV CM, DM
• DC I/O, AC I/O (shielded),analog
communication: 1kV CM
0.15M-80MHz, 80% AM modulation
@1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-
cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
*2
,