Mitsubishi Electric Q26UD(E)HCPU User Manual page 192

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

No.
Name
16)
Power input terminals
17)
Power input terminals
*1
Flicker-OFF indicates that the output signal of the terminal turns off and on at intervals of one second for three times and
then off (opens).
*2
When using the Q61P-D in the system configured with an extension base unit, the POWER LED of the Q61P-D on the
extension base unit may turn on in dull red when the module is turned off. Note that this does not indicate an error.
● The Q61P-A1 is dedicated for inputting a voltage of 100 VAC.
Do not input a voltage of 200 VAC into it or trouble may occur on the Q61P-A1.
Power supply
module
Q61P-A1
Q61P-A2
● Q64P automatically switches the input range 100/200VAC.
Therefore, it cannot be used in the intermediate voltage (133 to 169VAC).
The CPU module may not work normally if the above intermediate voltage is applied.
● Individually ground the LG and FG terminals with a ground resistance of 100  or less.
● When the Q61P-A1, Q61P-A2, Q61P-D, Q61P, Q62P, Q63P, Q64P or Q64PN is mounted on the extension base unit, a
system error cannot be detected by the ERR. terminal. (The ERR. terminal is always off.)
● Cables for the ERR. contact and LIFE OUT contact must be up to 30m and installed in the control panel.
190
Power input terminals for Q63P and connected to a 24VDC power supply.
Power input terminals for Q64P and connected to a 100VAC/200VAC power supply.
100VAC
Operates normally.
Power supply module does not cause trouble.
CPU module cannot be operated.
Application
Supply power voltage
Power supply module causes trouble.
Operates normally.
200VAC