Mitsubishi Electric Q26UD(E)HCPU User Manual page 362

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[PARAMETER ERROR]
• The high speed interrupt is set in a Q02CPU.
• The high speed interrupt is set in a multiple CPU
system.
• The high speed interrupt is set when a
QA1S6B or QA6B is used.
• No module is installed at the I/O address
designated by the high speed interrupt.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/At writing to
3006
programmable controller
[PARAMETER ERROR]
• No module is installed at the I/O address
designated by the high speed interrupt or the I/O
address is outside the range.
• The CPU device setting for high speed buffer
transfer is outside the range.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/At writing to
programmable controller
[PARAMETER ERROR]
The parameter file in the drive specified as valid
parameter drive by the DIP switches is
inapplicable for the CPU module.
■Collateral information
3007
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/At writing to
programmable controller
[PARAMETER ERROR]
In a multiple CPU system, the modules for AnS, A,
Q2AS and QnA have been set to multiple control
CPUs.
3009
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset
[PARAMETER ERROR]
The parameter-set number of CPU modules differs
from the actual number in a multiple CPU system.
■Collateral information
3010
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/At writing to
programmable controller
[PARAMETER ERROR]
Multiple CPU setting or control CPU setting differs
from that of the reference CPU settings in a
multiple CPU system.
■Collateral information
3012
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN/At writing to
programmable controller
360
Corrective action
• Delete the setting of the Q02CPU' s high
speed interrupt. To use high speed
interrupts, change the CPU module to one
of the Q02H/Q06H/Q12H/Q25HCPU.
• To use a multiple CPU system, delete the
setting of the high-speed interrupt. To use
high speed interrupts, change the system
to a single CPU system.
• To use either the QA1S6B or QA6B,
delete the setting of the high speed
interrupt.
• To use high speed interrupts, do not use
the QA1S6B/QA6B.
• Re-examine the I/O address designated by
the high speed interrupt setting.
• Re-examine the I/O address designated by
the high speed interrupt setting.
• Re-examine the buffer range designated by
the high speed interrupt setting.
Create parameters using the programming
tool and write them to the drive specified as a
parameter-valid drive by the DIP switches.
Re-set the parameter I/O assignment to
control them under one CPU module.
(Change the parameters of all CPUs in the
multiple CPU system.)
The number of CPU modules in the multiple
CPU system must be the same as the value
derived as follows: (the number of CPU
modules set in the multiple CPU setting) -
(the number of PLC (empty) slots set in the
I/O assignment).
Match the multiple CPU setting or control
CPU setting in the PLC parameter with that of
the reference CPU (CPU No.1) settings.
LED status,
Corresponding
CPU status
Qn(H)
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnUDV
RUN: Off
ERR.:Flashing
QnPRH
CPU Status:Stop
RUN: Off
ERR.:Flashing
Qn(H)
CPU Status:Stop
RUN: Off
ERR.:Flashing
Qn(H)
QnPH
CPU Status:Stop
RUN: Off
Q00/Q01
ERR.:Flashing
Qn(H)
CPU Status:Stop
CPU
QnU
QnU