Mitsubishi Electric Q26UD(E)HCPU User Manual page 210

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Item
Input power supply
Input frequency
Input voltage distortion
factor
Max. input apparent
power
*1
Inrush current
Rated output
5VDC
current
Overcurrent
5VDC
*1
protection
Overvoltage
5VDC
*1
protection
Efficiency
Allowable momentary
*1
power failure time
Dielectric withstand
voltage
Insulation resistance
• By noise simulator of 1500Vp-p noise voltage, 1µs noise width and 25 to 60Hz noise frequency
Noise durability
• Noise voltage IEC61000-4-4, 2KV
Operation indication
Fuse
Contact output section
Terminal screw size
Applicable wire size
Applicable solderless
RAV1.25 - 3.5, RAV2 - 3.5, thickness 0.8mm or less. Two solderless terminals can be connected to one terminal.
terminal
Applicable tightening
torque
External dimensions
Weight
*1
For the descriptions of the specification items, refer to Page 213, Section 7.2.2.
208
Q00JCPU (Power supply part)
Within 5% (
2300VAC per minute (altitude 0 to 2000m)
Between the combined "line input/LG terminals" and the "FG terminal and output"
10MΩ or higher by 500VDC insulation resistance tester
Between the combined "line input/LG terminals" and the "FG terminal and output", the line input and
LG terminals, the output and FG terminals
LED indication (The POWER LED of the CPU part: Normal: On (green), Error: Off)
Performance Specifications
Q00UJCPU (Power supply part)
+10%
100 to 240VAC
-15%
(85 to 264VAC)
50/60Hz ±5%
Page 103, Section 4.8.1)
105VA
40A within 8ms
3A
3.3A or more
5.5 to 6.5V
65% or more
Within 20ms (100VAC or more)
Built-in (User-unchangeable)
None
M3.5×7
2
0.75 to 2mm
0.66 to 0.89N•m
Page 145, Section 6.2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents