Mitsubishi Electric Q26UD(E)HCPU User Manual page 521

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Number
Name
Meaning
Battery life-
Battery life-
SD119
prolonging
prolonging
factor
factor
Bit pattern in
units of 16
points,
indicating the
modules
SD130
whose fuses
Fuse blown
to
have blown
module
SD137
0:
No
blown
fuse
1:
Blown
fuse
present
Bit pattern, in
units of 16
points,
SD150
I/O module
indicating the
to
verification
modules with
SD157
error
verify errors.
0:
No
error
1:
Error
Latest
volume of IP
packet
SD180
transferred
Latest
data (lower
volume of IP
digits)
packet
Latest
transferred
volume of IP
data
packet
SD181
transferred
data (upper
digits)
Explanation
This register stores a value indicating a cause that has the
battery life-prolonging function enabled. While this register is
other than "0", the battery life-prolonging function is enabled.
b15
to
b2 b1 b0
Fixed to 0
• This register stores the number of a fuse-blown output
module (in units of 16 points) in the following bit pattern. (If
the module numbers are set by parameter, the parameter-
set numbers are stored.)
b15 b14 b13 b12 b11b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1
1
0
0
0
0
0
0
0
SD130
(YC0)
(Y80)
1
1
SD131
0
0
0
0
0
0
0
(Y1F0)
(Y1A0)
1
0
0
0
0
0
0
0
0
SD137
(Y7B0)
Indicates a fuse blown state.
For a module whose number of output points exceeds 16
points, only the bit corresponding to the output module
number within the number of output points occupied by the
module (in increments of 16 points) turns on.
Example: When a 64-point module is mounted on the slot 0,
only b0 turns on when the fuse has blown.
• Not cleared even if the blown fuse is replaced with a new
one. The storage value is cleared by clearing the error.
• If the status of the I/O module changes from that obtained at
power-on, the module No. (unit: 16 points) is stored in the
following bit pattern. (When I/O module numbers have been
set by the parameter, the parameter-set numbers are
stored.)
b15 b14 b13 b12 b11 b10 b9
b8
b7
SD150
0
0
0
0
0
0
0
0
0
1
SD151
0
0
0
0
0
0
0
0
X Y
(
)
190
1
SD157
0
0
0
0
0
0
0
0
X Y
(
)
7E0
Indicates an I/O module verify error.
For a module whose number of I/O points exceeds 16 points,
only the bit corresponding to the I/O module number within the
number of I/O points occupied by the module (in increments of
16 points) turns on.
Example: When a 64-point module is mounted on the slot 0,
only b0 turns on when an error is detected.
• Not cleared even if the blown fuse is replaced with a new
one. The storage value is cleared by clearing the error.
The latest value of total IP packet size (byte), which was
transferred per unit time (1 second), is stored.
Range: 0 to 4294967295 (FFFFFFFF
Set by
(When Set)
S (Status
0:No factor
1:Foctor
change)
b0: CPU switch setting
b1: Backup in execution by
latch data backup function
(to standard ROM)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
S (Error)
(Y730)
b6
b5
b4
b3
b2
b1
b0
1
0
0
0
0
0
0
X Y
(
)
0
0
0
0
0
0
0
0
S (Error)
0
0
0
0
0
0
0
S (Status
change)
)
H
APPENDICES
Corresponding
Corresponding
ACPU
CPU
D9
QnU (except
New
QnUDV)
LCPU
New
Q00J/Q00/Q01
New
Q00J/Q00/Q01
*5
QnU
New
*6
LCPU
519
A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents