Error code
Error item
(Hexadecimal)
Predefined
C405
protocol related
H
error (Ethernet)
Predefined
C410
protocol related
H
error (Ethernet)
Predefined
C417
protocol related
H
error (Ethernet)
Predefined
C430
protocol related
H
error (Ethernet)
Predefined
C431
protocol related
H
error (Ethernet)
iQ Sensor
CEE0
Solution related
H
error
iQ Sensor
CEE1
Solution related
H
error
iQ Sensor
CEE2
Solution related
H
error
Error details
Setting value of protocol No. specified when
protocol was executed is out of range.
Receive wait time was up.
Setting value in Data Length Storage Area, Data
Quantity Storage Area is out of range.
Protocol setting data check occurred while
SP.ECPRTCL instruction is executed.
Connection close occurred while SP.ECPRTCL
instruction is executed.
While the automatic detection is being
performed, the automatic detection or another iQ
Sensor Solution function was executed by
another peripheral.
System error
System error
Corrective action
Execute the protocol again after checking the
specified protocol No.
• Check whether the cable is connected.
• Check the setting of specified connection No.,
execute protocol again if there aren't any
problem found.
• Check whether any errors are found in the target
device.
• Check whether the sending data from the target
device has not been interrupted.
• Check whether any of data were lost because of
receive error.
• Check whether the send data (packet) from the
target device is correct.
• Check the maximum data length for Data Length
Storage Area, reset a value within the range.
• Check the maximum number of data for Data
Quantity Storage Area, reset a value within the
range.
• Cancel the instruction and check the protocol
setting data while SP.ECPRTCL is being
executed.
• Check the behavior of the target device.
• Check the connection open status with the
target device.
• Execute the instruction after opening the
connection again with the target device.
Execute the function after the automatic detection
that is currently being performed ends.
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Check the connection status of each Ethernet
cable and the hub.
• Check the line status of Ethernet.
• Reset the CPU module and devices supporting
iQ Sensor Solution, and execute the function
again.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Check the connection status of each Ethernet
cable and the hub.
• Check the line status of Ethernet.
• Reset the CPU module and devices supporting
iQ Sensor Solution, and execute the function
again.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
APPENDICES
Corresponding
CPU
A
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
449