Mitsubishi Electric Q26UD(E)HCPU User Manual page 376

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[REMOTE PASS. ERR.]
Any of the following modules is not mounted in the
slot specified by the start I/O number of the remote
password target module.
• Serial communication module whose function
version B or later
• Ethernet module whose function version B or
later
■Collateral information
• Common information: -
• Individual information: -
3401
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[REMOTE PASS. ERR.]
Serial communication module or Ethernet module
of function version B or later controlled by another
CPU was specified in a multiple CPU system.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
*1
The parameter No. will be the number obtained by the formula: "start I/O number of the intelligent function module set in
parameter using GX Configurator"  10
*2
The diagnostic timing of CPU modules other than the Universal model QCPU and LCPU is only when the status of the
CPU module is switched from STOP to RUN.
374
Corrective action
Mount the following modules in the slot
specified by the start I/O number of the
remote password target module.
• Serial communication module whose
function version B or later
• Ethernet module whose function version B
or later
• Change it for the Ethernet module of
function version B or later connected by the
host CPU.
• Delete the remote password setting.
.
H
LED status,
Corresponding
CPU status
Q00J/Q00/Q01
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
CPU
QnU