Mitsubishi Electric Q26UD(E)HCPU User Manual page 63

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

(b) In case of slim type main base unit
*4
*2, *6
17mm or more
*1
For wiring duct with 50mm or less height.
40mm or more for other cases.
*2
The cable of the power supply module of the slim type main base unit protrudes out of the left end of the module. Install
the module while reserving 17mm or more wiring space.
If the cable sheath is susceptible to damage caused by a structural object or part on the left side of the module, take a
protective measure with spiral tube or a similar insulator.
*3
80mm or more for the connector type. 80mm or more for installing the Q8BAT cable when using the Q8BAT.
*4
45mm or more when the Q7BAT is mounted.
*5
30mm or more from the top and bottom of the Q8BAT when the Q8BAT is mounted.
*6
5mm or more from the right and left of the Q8BAT when the Q8BAT is mounted.
(2) Module mounting orientation
• To ensure good ventilation for heat dispassion, install the programmable controller in the orientation as
shown below.
• Do not mount the programmable controller in the orientations as shown below.
Indicates the control panel top,
wiring duct or any part position.
*5, *6
5mm or more
Vertical mounting
CHAPTER 4 INSTALLATION AND WIRING
30mm or
*1, *5
more
Control
panel
30mm or
*4, *5
more
*6
Horizontal installation
Programmable
controller
Door
20mm or
*3
more