Error code
Error item
(Hexadecimal)
iQ Sensor
CF10
Solution related
H
error
iQ Sensor
CF20
Solution related
H
error
iQ Sensor
CF30
Solution related
H
error
iQ Sensor
CF31
Solution related
H
error
iQ Sensor
CF41
Solution related
H
error
iQ Sensor
CF50
Solution related
H
error
iQ Sensor
CF51
Solution related
H
error
450
Error details
System error
• The communication setting value is out of the
range.
• The communication setting item not supported
by the target device supporting iQ Sensor
Solution is set.
• The setting item required for the target device
supporting iQ Sensor Solution is not set.
A parameter not supported by the target device
supporting iQ Sensor Solution was specified.
System error
The information required for monitoring cannot
be read from the device supporting iQ Sensor
Solution.
System error
The function cannot be executed because the
function from another peripheral is being
executed.
Corrective action
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Check the connection status of each Ethernet
cable and the hub.
• Check the line status of Ethernet.
• Reset the CPU module and devices supporting
iQ Sensor Solution, and execute the function
again.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
Review the settings, and execute the function
again.
Check the version of the device supporting iQ
Sensor Solution.
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Check the connection status of each Ethernet
cable and the hub.
• Check the line status of Ethernet.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Reset the devices supporting iQ Sensor
Solution, and execute the function again.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
• Check the operating status and connection
status of each device supporting iQ Sensor
Solution.
• Check the connection status of each Ethernet
cable and the hub.
• Check the line status of Ethernet.
• Reset the CPU module and devices supporting
iQ Sensor Solution, and execute the function
again.
• If the same error code is displayed again even
after the above actions are taken, please consult
the manufacturer of the device supporting iQ
Sensor Solution.
Execute the function again after a while.
Corresponding
CPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU
QnUDV
LCPU

Hide quick links: