(6) CC-Link module
• Be sure to ground the cable shield that is connected to the CC-Link module close to the exit of control panel
or to any of the CC-Link stations within 30cm from the module or stations.
The CC-Link dedicated cable is a shielded cable. Remove a part of the jacket as shown below and ground
the exposed shield section to the ground as much as possible.
• Always use the specified CC-Link dedicated cable.
• Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line
inside the control panel.
Terminating resistor
• Use a CE-marked power supply to which the module power supply or external power supply is connected.
Ground the FG terminals.
Power supply model name
Rated input voltage
Rated output
• Each power line connecting to the external power supply terminal or module power supply terminal must be
30m or less.
• Install a noise filter to the external power supply. Use the noise filter having an attenuation characteristic,
MA1206 (TDK-Lambda) or equivalent. Note that a noise filter is not required if the module is used in Zone A
defined in EN61131-2.
• Keep the length of signal cables connected to the analog input terminals of the following modules to 30m or
less. Wire cables connected to the external power supply and module power supply terminal in the control
panel where the module is installed.
AJ65BT-64RD3
AJ65BT-64RD4
AJ65BT-68TD
• For the cable connected to the power supply terminal of the AJ65SBT-RPS, AJ65SBT-RPG or AJ65BT-
68TD, install a ferrite core with attenuation characteristic equivalent to that of the ZCAT3035-1330 from TDK
Corporation. Twist the cable around the ferrite core by one as shown below.
658
Master module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
CC-Link
FG
dedicated
cable
DLP75-24-1
Voltage
Current
3.1A
CC-Link dedicated cable
Shield
Remote module
Local module
DA
DB
DG
SLD
CC-Link
FG
dedicated
cable
DLP100-24-1
DLP120-24-1
100 to 240VAC
24VDC
4.1A
DA
Terminating resistor
DB
DG
SLD
FG
DLP180-24-1
5.0A
7.5A
DLP240-24-1
10.0A