Item
Latch range
RUN/PAUSE contact
Clock function
Allowable momentary power failure
time
5VDC internal current consumption
H
External dimensions
W
D
Weight
Remark
For the general specifications, refer to Page 117, CHAPTER 5.
Q02PHCPU
Q06PHCPU
(Latch range can be set up for B, F, V, T, ST, C, D, and W.) (Setting by parameters)
One contact can be set up in X0 to 1FFF for each of RUN and PAUSE. (Setting by parameters)
Year, month, date, hour, minute, second, and day of the week
(Automatic leap year detection)
Accuracy: -3.18 to +5.25s(TYP.+2.12s)/d at 0°C
Accuracy: -3.93 to +5.25s(TYP.+1.90s)/d at 25°C
Accuracy: -14.69 to +3.53s(TYP.-3.67s)/d at 55°C
Varies depending on the power supply module.
CHAPTER 6 CPU MODULE
Process CPU
Q12PHCPU
L0 to 8191 (default)
0.64A
98mm
27.4mm
89.3mm
0.20kg
Q25PHCPU
6
155