(3) Special relays and special register related to online module change
Information during online module change is stored into the special relays (SM235, SM236) and special register
(SD235).
• Whether the online module change of the corresponding CPU module is executed or not can be checked by
monitoring SM235, SM236 and SD235.
• SM235: Online module change flag (turns on during online module change)
• SM236: Flag that turns on only one scan after online module change (turns on only one scan after
completion of online module change)
• SD235: Module being changed online (stores the starting I/O number of the module being changed
online10
)
H
Refer to Page 454, Appendix 2 for details of SM235 and SM236 and to Page 506, Appendix 3 for details of
SD235.
SM235
OFF
SD235
SM236
OFF
CHAPTER 14 MODULE CHANGE DURING SYSTEM OPERATION
Online module
change start
ON
Starting I/O number of module being
changed online
10
H
Online module
change completed
ON
1 scan
269
14