Mitsubishi Electric Q26UD(E)HCPU User Manual page 366

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[LINK PARA. ERROR]
• Although the CC-Link IE module is mounted,
network parameter for the CC-Link IE module is
not set.
• Although the CC-Link IE and MELSECNET/H
modules are mounted, network parameter for
the MELSECNET/H module is not set.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• Although the CC-Link IE module is mounted,
network parameter for the CC-Link IE module is
not set.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
3100
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
In a multiple CPU system, the MELSECNET/H
under control of another CPU is specified as the
start I/O number in the network setting parameter
of the MELSECNET/H.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
The network parameter of the MELSECNET/H
operating as the normal station is overwritten to
the control station. Or, the network parameter of
the MELSECNET/H operating as the control
station is overwritten to the normal station. (The
network parameter is updated on the module by
resetting.)
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
364
Corrective action
• Check the network parameters and actual
mounting status, and if they differ, make
them matched. If any of the network
parameters is corrected, write it to the CPU
module.
• Check the set number of extension base
units.
• Check the connection status of the
extension base units and extension cables.
Check the connection of the GOT if it is
bus-connected to the main base unit or
extension base unit.
If an error occurs even after taking the above
measures, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
• Check the network parameters and actual
mounting status, and if they differ, make
them matched. If any of the network
parameters is corrected, write it to the CPU
module.
If an error occurs even after taking the above
measures, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
• Delete the MELSECNET/H network
parameter of the MELSECNET/H under
control of another CPU.
• Change the setting to the start I/O number
of the MELSECNET/H under control of the
host CPU.
Reset the CPU module.
LED status,
Corresponding
CPU status
Qn(H)
QnPH
QnPRH
LCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
Qn(H)
QnPH
QnPRH
CPU
QnU
QnU
QnU

Hide quick links: