(3) Installation surface
Install the base unit on a flat surface. If the surface where the base unit is installed is not even, this may strain the
printed circuit boards and cause malfunctions.
(4) Installation in an area where other devices are installed
Do not install a base unit in proximity to vibration sources such as large magnetic contractors and no-fuse circuit
breakers. Install a base unit on a separate control panel or away from vibration sources.
(5) Distances from other devices
In order to avoid the effects of radiated noise and heat, provide the clearances indicated below between the
programmable controller and devices that generate noise or heat (contactors and relays).
• Required clearance in front of programmable controller : at least 100mm
• Required clearance on the right and left of programmable controller : at least 50mm
At least
100mm
Contactor, relay, etc.
*1
When using a Redundant CPU, keep a distance of 100mm or more between the programmable controller and the
tracking cable.