Error
Error and cause
code
[MULTI-COM. ERROR]
The number of read/write data (number of
request/receive data) for the multiple CPU high-
speed transmission dedicated instruction specified
by the program is not valid.
4355
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[SFCP. CODE ERROR]
No SFCP or SFCPEND instruction in SFC
program.
■Collateral information
4400
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• STOP  RUN
[CAN'T SET(BL)]
The block number designated by the SFC program
exceeds the range.
■Collateral information
4410
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[CAN'T SET(BL)]
Block number designations overlap in SFC
program.
■Collateral information
4411
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[CAN'T SET(S)]
A step number designated in an SFC program
exceeds the range.
■Collateral information
4420
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[CAN'T SET(S)]
The number of steps in the SFC program exceeds
the total number of step relays.
■Collateral information
4421
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[CAN'T SET(S)]
Step number designations overlap in SFC
program.
■Collateral information
4422
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[CAN'T SET(S)]
The total number of (maximum step No.+1) of
each block exceeds the total number of step
relays.
4423
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP  RUN
386
Corrective action
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Write the program to the CPU module again
using the programming tool.
Write the program to the CPU module again
using the programming tool.
Write the program to the CPU module again
using the programming tool.
Write the program to the CPU module again
using the programming tool.
Correct the program so that the number of
steps in the SFC program may not exceed
the total number of step relays.
Increase the total number of step relays in the
Device tab of "PLC Parameter".
Write the program to the CPU module again
using the programming tool.
Correct the total number of step relays so that
it does not exceed the total number of
(maximum step No.+1) of each block.
Increase the total number of step relays in the
Device tab of "PLC Parameter".
LED status,
Corresponding
CPU status
RUN: Off
ERR.:Flashing
CPU Status:Stop
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
LCPU
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
LCPU
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
LCPU
Q00J/Q00/Q01
Qn(H)
QnPH
RUN: Off
QnPRH
ERR.:Flashing
LCPU
CPU Status:Stop
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
LCPU
Q00J/Q00/Q01
LCPU
RUN: Off
ERR.:Flashing
CPU Status:Stop
CPU
QnU
QnU
QnU
QnU
QnU
QnU
QnU
QnU
QnU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents