Mitsubishi Electric Q26UD(E)HCPU User Manual page 570

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Number
Name
Meaning
Stores
Operation
SD1270
operation
result
result.
SD1271
SD1272
Stores time
Execution
acquired with
time
time setting
SD1273
function.
SD1274
Stores time
Required
required for
SD1275
response
clock time
time
acquisition.
568
Explanation
This register stores the operation result of the time setting
function.
• 0: Not executed
• 1: Success
0FFFF
: Failure
H
This register stores the year (last two digits) and the month
that the time setting function was executed in 2-digit BCD.
b15
to
b12 b11
to
b8 b7
to
b4 b3
Year
Month
This register stores the day and the hour that the time setting
function was executed in a 2-digit BCD.
b15
to
b12 b11
to
b8 b7
to
b4 b3
Day
Hour
This register stores the minute and the second that the time
setting function was executed in a 2-digit BCD.
b15
to
b12 b11
to
b8 b7
to
b4 b3
Minute
Second
This register stores the year (first two digits) and the day of
the week that the time setting was executed in 2-digit BCD.
b15
to
b12 b11
to
b8 b7
to
b4 b3
Higher digits of year (0 to 99)
This register stores the time required for a clock value to be
set on the CPU after being sent to the SNTP server.
• Range: A0 to 0FFFE
(Unit: ms)
H
0FFFF
when the above limit is exceeded.
H
This register stores a value only when the operation is
succeeded. (When failed, a previous value remains.)
Set by
(When Set)
Example:
to
b0
July, 1993
9307H
Example:
to
b0
31st, 10 a.m.
3110H
S (Status
to
b0
Example:
change)
35 min., 48 sec.
3548H
to
b0
Example:
1993, Friday
1905H
Day of the week
0
Sunday
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
Corresponding
Corresponding
ACPU
CPU
D9
*1
QnU
New
*1
LCPU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents