4.3.4
Voltage drop when an extension base unit is used
Since the extension base unit (Q5B or QA1S5B) is supplied with 5VDC from the power supply module on the main
base unit, a voltage drop occurs at extension cables. Improper I/O may occur if the specified voltage (4.75VDC or
higher) is not supplied to the "IN" connector of the Q5B or QA1S5B.
When using the Q5B or QA1S5B, make sure that the "IN" connector of the Q5B or QA1S5B is supplied with
4.75VDC or higher.
And it is recommended to connect either of the extension base units as close as possible to the main base unit by
using the short extension cable, so as to minimize the effects of voltage drop.
(1) When only the Q5B or QA1S5B is connected to the extension base unit
(a) Selection condition
4.75VDC or higher must be supplied to the "IN" connector of the Q5B or QA1S5B in the final extension
base.
88