Mitsubishi Electric Q26UD(E)HCPU User Manual page 369

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[LINK PARA. ERROR]
A CC-Link IE module parameter error was
detected.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• The network module detected a network
parameter error.
• A MELSECNET/H network parameter error was
detected.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
The station No. specified in pairing setting are not
correct.
• The stations are not numbered consecutively.
• Pairing setting has not been made for the CPU
module at the normal station.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
The CC-Link IE Controller Network module whose
first 5 digits of serial No. is "09041" or earlier is
3102
mounted.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
• Different network types are set between the
control station and the normal station (CC IE
Control Ext. Mode/Normal Mode).
• The parameter in which "CC IE Control Ext.
Mode" is set for "Network Type" was transferred
to the CPU module that does not support the
send points expansion function.
• The parameter in which "CC IE Control Ext.
Mode" is set was backed up to a memory card
or GOT and then restored to the CPU module
that does not support the send points expansion
function.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[LINK PARA. ERROR]
Group cyclic function in CC-Link IE Controller
Network that does not correspond to group cyclic
function is set.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
Corrective action
• Correct and write the network parameters.
• If an error occurs again even after it is
corrected, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
Refer to the troubleshooting of the network
module, and if the error is due to incorrect
pairing setting, reexamine the pairing setting
of the network parameter.
Mount the CC-Link IE Controller Network
module whose first 5 digits of serial No. is
"09042" or later.
• Set the same network type (CC IE Control
Ext. Mode/Normal Mode) for the control
station and the normal station.
• Do not use the parameter in which "CC IE
Control Ext. Mode" is set for "Network
Type" for the CPU module that does not
support the send points expansion function.
Or, use the CPU module and the CC-Link
IE Controller Network module that support
the send points expansion function in the
same network.
Set group cyclic function in function version D
or later of CC-Link IE Controller Network.
APPENDICES
LED status,
Corresponding
CPU status
CPU
Qn(H)
QnPH
QnPRH
QnU
LCPU
QCPU
QnPRH
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
A
367