2) Conditions of a program
The following tables list devices used in a program for monitoring the module life.
Signal
Monitoring clear command
Life warning signal
Error signal
Signal
LIFE OUT signal
Monitoring clear request
Monitoring start flag
Time monitoring flag
ON/OFF monitoring timer
ON/OFF counter
When the life detection function of the Q61P-D is faulty, the LIFE OUT terminal repeats on and off for three times when the
module is started.
Depending on the system, this behavior (on and off) of the LIFE OUT terminal may not be obtained to the input module due
to delay of the sequence program start after the Q61P-D has started.
In this program example, M11 turns on even though the life detection function is faulty when powered on since the remaining
life is regarded as one year.
Device
X0F
Resets the life monitoring processing
Turns on when the remaining life of the Q61P-D is one
M11
year or less
Turns on when the life detection function of the Q61P-
M12
D is faulty
Device
X00
LIFE OUT terminal status of the Q61P-D
An internal signal for resetting the life monitoring
M0
processing
An internal signal for detecting offs of the LIFE OUT
M1
terminal
An internal signal for counting on and off of the LIFE
M2
OUT terminal
On and off of the LIFE OUT terminal are counted while
T0
this timer is enabled (6 seconds)
D100
Counts on and off of the LIFE OUT terminal
CHAPTER 7 POWER SUPPLY MODULE
Function
Function
7
221