Mitsubishi Electric Q26UD(E)HCPU User Manual page 398

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[TRK. TRANS. ERR.]
• A timeout error occurred in tracking (data
transmission). (This error may be caused by
tracking cable removal or other system power-
off (including reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
6101
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
• Common information: Tracking transmission
data classification
• Individual information: -
■Diagnostic timing
• Always
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception). (This can be detected from the control
system or standby system of the redundant
system.)
6102
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[TRK. TRANS. ERR.]
• A data error (other than sum value error)
occurred in tracking (data reception). (This error
may be caused by tracking cable removal or
other system power-off (including reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
6103
followed.
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[TRK. TRANS. ERR.]
• An error (e.g. retry limit exceeded) occurred in
tracking (data transmission). (This error may be
caused by tracking cable removal or other
system power-off (including reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
6105
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
• Common information: Tracking transmission
data classification
• Individual information: -
■Diagnostic timing
• Always
396
Corrective action
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
LED status,
Corresponding
CPU status
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
CPU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents