Error
Error and cause
code
[TRK. TRANS. ERR.]
• A timeout error occurred in tracking (data
transmission). (This error may be caused by
tracking cable removal or other system power-
off (including reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
followed.
6106
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
• Common information: Tracking transmission
data classification
• Individual information: -
■Diagnostic timing
• Always
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception). (This can be detected from the control
system or standby system of the redundant
system.)
6107
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[TRK. TRANS. ERR.]
• A data error (other than sum value error)
occurred in tracking (data reception). (This error
may be caused by tracking cable removal or
other system power-off (including reset).)
• The error occurred at a startup since the
redundant system startup procedure was not
6108
followed.
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[TRK. SIZE ERROR]
The tracking capacity exceeded the allowed
range. (This can be detected from the control
system or standby system of the redundant
system.)
6110
■Collateral information
• Common information: Reason(s) for tracking
size excess error
• Individual information: -
■Diagnostic timing
• When an END instruction executed
[TRK. SIZE ERROR]
The control system does not have enough file
register capacity for the file registers specified in
the tracking settings. (This can be detected from
the control system or standby system of the
6111
redundant system.)
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• When an END instruction executed
Corrective action
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
• Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
• Confirm the redundant system startup
procedure, and execute a startup again.
Reexamine the tracking capacity.
Switch to the file registers of which capacity is
greater than the file registers specified in the
tracking settings.
APPENDICES
LED status,
Corresponding
CPU status
CPU
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
RUN: On
ERR.:On
QnPRH
CPU Status:Continue
A
397

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents