Mitsubishi Electric Q26UD(E)HCPU User Manual page 324

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[CONTROL-BUS ERR.]
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[CONTROL-BUS ERR.]
1413
(1)
An error is detected on the system bus.
• Self-diagnostic error in the system bus
• Self-diagnostic error in the CPU module
(2)
In a multiple CPU system, the control CPU
setting of other CPUs, configured in the I/O
Assignment tab of "PLC Parameter", differs
from that of CPU No.1.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[CONTROL-BUS ERR.]
• Fault of a loaded module was detected.
• In a multiple CPU system, a CPU module
incompatible with the multiple CPU system is
mounted.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• Always
1414
[CONTROL-BUS ERR.]
An error is detected on the system bus.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• Always
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
■Collateral information
• Common information: Module No. (Base No.)
• Individual information: -
■Diagnostic timing
• Always
1415
[CONTROL-BUS ERR.]
Fault of the main or extension base unit was
detected.
■Collateral information
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• At power-on/At reset/When an END instruction
executed
322
Corrective action
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• The cause is a failure of the intelligent
function module, CPU module, or base
unit. Please consult your local Mitsubishi
representative.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
• Reconfigure the control CPU setting of
other CPUs so that it can be the same as
that of CPU No.1.
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
• Remove the CPU module from the main
base unit if it does not support a multiple
CPU system configuration. Alternatively,
replace the CPU module that does not
support a multiple system configuration
with the one that does.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi
representative.
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a failure of the intelligent function
module, CPU module, or base unit. Please
consult your local Mitsubishi representative.
LED status,
Corresponding
CPU status
Q00J/Q00/Q01
Qn(H)
QnPH
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
Q00J/Q00/Q01
Qn(H)
QnPH
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
CPU
QnU
QnU
QnU
*7
*7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents