Mitsubishi Electric Q26UD(E)HCPU User Manual page 321

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[I/O INT. ERROR]
An interrupt request was detected from the module
for which Interrupt Pointer Setting has not been
configured in "PLC Parameter".
1311
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• During interrupt
[LAN CTRL. DOWN]
The H/W self-diagnostics detected a LAN
controller failure.
■Collateral information
1320
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
[LAN CTRL. DOWN]
The H/W self-diagnostics detected a LAN
controller failure.
■Collateral information
1321
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Corrective action
• Correct the interrupt pointer setting in the
PLC System tab of "PLC Parameter".
• Take measures not to issue an interruption
from the modules where the interrupt
pointer setting is not configured in the PLC
System tab of "PLC Parameter".
• Correct the interrupt setting of the network
parameter.
• Correct the interrupt setting of the
intelligent function module buffer memory.
• Correct the basic program of the QD51.
• Correct the interrupt pointer setting in the
PLC System tab of "PLC Parameter".
• Take measures not to issue an interruption
from the modules where the interrupt
pointer setting is not configured in the PLC
System tab of "PLC Parameter".
• Correct the Interrupt Setting of the network
parameter.
• Correct the interrupt setting of the
intelligent function module buffer memory.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
The cause is a hardware failure of the CPU
module. Please consult your local Mitsubishi
representative.
APPENDICES
LED status,
Corresponding
CPU status
CPU
Q00J/Q00/Q01
QnPRH
QnU
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QnU
LCPU
CPU Status:Stop
RUN: Off
ERR.:Flashing
QnU
LCPU
CPU Status:Stop
A
*4
*4
*4
*4
319