Mitsubishi Electric Q26UD(E)HCPU User Manual page 381

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Error
Error and cause
code
[OPERATION ERROR]
In a multiple CPU system, the link direct device
(J\) was specified for the network module
under control of another station.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
• The module No./network No. /station No.
specified for the dedicated instruction is wrong.
• The link direct device (J\) setting is
incorrect.
• The module No./network No./number of
4102
character strings exceeds the range that can be
specified.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
The character string (" ") specified by a dedicated
instruction cannot be used for the character string.
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
The configuration of the PID dedicated instruction
is incorrect.
■Collateral information
4103
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
PLOADP/PUNLOADP/PSWAPP instructions were
executed while setting program memory check.
■Collateral information
4105
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
33 or more multiple CPU dedicated instructions
were executed from one CPU module.
■Collateral information
4107
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
[OPERATION ERROR]
With high speed interrupt setting PR, PRC,
UDCNT1, UDCNT2, PLSY or PWM instruction is
executed.
4109
■Collateral information
• Common information: Program error location
• Individual information: -
■Diagnostic timing
• When instruction executed
Corrective action
• Delete from the program the link direct
device which specifies the network module
under control of another CPU.
• Using the link direct device, specify the
network module controlled by the own
station.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
Read common information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value, and
correct it as necessary.
• Delete the setting for the program memory
check.
• When using the program memory check,
delete PLOADP/PUNLOADP/PSWAPP
instructions.
Using the multiple CPU dedicated instruction
completion bit, provide interlocks to prevent
one CPU module from executing 33 or more
multiple CPU dedicated instructions.
Delete the high-speed interrupt setting.
When using high-speed interrupt, delete the
PR, PRC, UDCNT1, UDCNT2, PLSY and
PWM instructions.
APPENDICES
LED status,
Corresponding
CPU status
CPU
Q00/Q01
Qn(H)
QnPH
QnU
RUN: Off/On
ERR.:Flashing/On
QCPU
CPU Status:
LCPU
*1
Stop/Continue
QnU
LCPU
RUN: Off/On
Q00J/Q00/Q01
ERR.:Flashing/On
Qn(H)
QnPRH
CPU Status:
QnU
*1
LCPU
Stop/Continue
RUN: Off/On
ERR.:Flashing/On
QnPH
CPU Status:
Stop/Continue
Q00/Q01