5.2
Power supply capacity and generated loss
Power supply capacity
Calculate the power supply capacity from the capacity of the converter unit.
MR-CV Power Regeneration Converter Unit User's Manual
Generated loss
Amount of heat generated by the drive unit
The following tables indicate the losses generated by drive units under rated load. For thermal design of an enclosed type
cabinet, use the values in the tables in consideration for the harshest conditions with regard to the environment and operation
pattern. The actual amount of generated heat depends on the frequency of operation and will be between the "At rated output"
and "At servo-off" values.
■400 V class
• 1-axis drive unit
Drive unit
MR-J5D1-100_
MR-J5D1-200_
MR-J5D1-350_
MR-J5D1-500_
MR-J5D1-700_
• Multi-axis drive unit
Drive unit
MR-J5D2-100_
MR-J5D2-200_
MR-J5D2-350_
MR-J5D2-500_
MR-J5D2-700_
MR-J5D3-100_
MR-J5D3-200_
5 CHARACTERISTICS
94
5.2 Power supply capacity and generated loss
Drive unit generated heat [W]
At rated output
100
150
210
380
450
Drive unit generated heat [W]
At rated output
Connected to one axis: 100
Connected to two axes: 170
Connected to one axis: 150
Connected to two axes: 270
Connected to one axis: 210
Connected to two axes: 390
Connected to one axis: 380
Connected to two axes: 730
Connected to one axis: 450
Connected to two axes: 870
Connected to one axis: 100
Connected to two axes: 170
Connected to three axes: 240
Connected to one axis: 150
Connected to two axes: 270
Connected to three axes: 390
At servo-off
30
30
30
30
30
At servo-off
30
30
30
30
30
30
30
Area required for heat
2
dissipation [m
]
2
3
4.2
7.6
9
Area required for heat
2
dissipation [m
]
3.4
5.4
7.8
14.6
17.4
4.8
7.8