15 TROUBLESHOOTING
LED
Classifica
Error
indicator
tion of
code
of servo
errors
amplifier
2035
35
2036
36
2037
37
Servo
amplifier
errors
2045
45
2046
46
2047
47
Error name
Command
Input pulse frequency of command
frequency error
pulse is too high.
Receive error 2
SSCNET
Parameter error Parameter setting is wrong.
Main circuit
device over
Main circuit device overheat
heated
Servomotor
Servomotor temperature rise
overheate
actuated the thermal protector.
The cooling fan of the servo amplifier
Cooling fan
stopped, or its speed decreased to or
alarm
below the alarm level.
Description
communication error
15 - 44
MELSEC-Q
Cause
Command given is greater than the
maximum speed of the servomotor.
Noise has entered the SSCNET
cable.
Fault in the QD75MH.
The SSCNET
cable is
disconnected.
The surface at the end of SSCNET
cable got dirty.
The SSCNET
cable is broken or
severed.
Noise entered the servo amplifier.
Servo amplifier fault caused the
parameter setting to be rewritten.
Parameter data mis-setting by
QD75MH.
The number of write times to EEP-
ROM exceeded 100,000 due to
parameter write, etc.
Servo amplifier faulty.
The power supply was turned on
and off continuously by overloaded
status.
Ambient temperature of servo
amplifier is over 55°C.
Used beyond the specifications of
close mounting.
Servomotor ambient temperature
exceeded the operating value of
40°C.
Servomotor overloaded.
Thermal protector in encoder is
faulty.
Cooling fan life expiration.
Foreign matter caught in the fan
stopped rotation.
The power supply of the cooling
fan failed.