Mitsubishi Electric Q66DA-G User Manual
Mitsubishi Electric Q66DA-G User Manual

Mitsubishi Electric Q66DA-G User Manual

Channel isolated digital-analog converter module
Hide thumbs Also See for Q66DA-G:

Advertisement

Quick Links

Digital-Analog Converter Module
Thank you for buying the Mitsubishi general-purpose programmable
controller MELSEC-Q Series.
Prior to use, please read both this manual and detailed manual
thoroughly and familiarize yourself with the product.
© 2006 MITSUBISHI ELECTRIC CORPORATION
Channel Isolated
User's Manual
MODEL
Q-66D/A-G-U-HW
MODEL
CODE
IB(NA)-0800362-E(0908)MEE
(Hardware)
Q66DA-G
13JY12

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric Q66DA-G

  • Page 1 Thank you for buying the Mitsubishi general-purpose programmable controller MELSEC-Q Series. Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product. MODEL Q-66D/A-G-U-HW MODEL 13JY12 CODE IB(NA)-0800362-E(0908)MEE © 2006 MITSUBISHI ELECTRIC CORPORATION...
  • Page 2 SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the programmable controller system, please read the user's manual for the CPU module to use In this manual, the safety instructions are ranked as "DANGER"...
  • Page 3 [Installation Precautions] CAUTION Use the programmable controller in an environment that meets the general specifications given in the User's Manual of the CPU module being used. Using this programmable controller in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product.
  • Page 4 [Wiring Precautions] CAUTION Always ground the FG terminal for the programmable controller. There is a risk of electric shock or malfunction. Tighten the screws within the range of specified torque. If the screws are loose, it may cause the module to fallout, short circuits, or malfunction.
  • Page 5 Section 5.3 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
  • Page 6: Table Of Contents

    CONTENTS 1. Overview ......................1 2. Performance Specifications ................2 3. Part Names..................... 5 4. Handling Precautions..................6 4.1 Mounting module fixing bracket..............7 5. Wiring......................8 5.1 Wiring precautions..................8 5.2 External wiring ..................9 5.3 Intelligent Function Module Switch Setting..........10 6.
  • Page 7 ABOUT MANUAL The following manuals is also related to this product. In necessary, order it by quoting the details in the table below. Relevant Manual Manual number Manual name (Model code) Channel Isolated Digital-Analog Converter Module User's SH-080648ENG ManualQ66DA-G / GX Configurator-DA (13JR97) Conformance to the EMC Directive/Low Voltage Directive (1) For programmable controller system...
  • Page 8: Overview

    This manual describes the specifications and the names of the components and handling for the Q66DA-G channel isolated digital-analog converter module (hereafter referred to as Q66DA-G) which are used in combination with the MELSEC-Q series CPU module. After unpacking, confirm that the following products are enclosed.
  • Page 9: Performance Specifications

    2. Performance Specifications The specifications for the Q66DA-G are shown in the following table. For general specifications, refer to the operation manual for the CPU module being used. Table 2.1 Performance Specifications Item Specifications 6 points (6 channels) Number of analog outputs...
  • Page 10 Table 2.1 Performance Specifications (Continued) Item Specifications Absolute Voltage maximum Current 23mA output Maximum number of MAX. 50,000 times writes to flash memory Output short-circuit Available protection Dielectric Isolation Insulation Specific isolated area withstand method resistance voltage Between the output terminal and 500VAC programmable controller power supply rms, 1min.
  • Page 11 *1:Accuracy of offset/gain setting at ambient temperature Q66DA-G needs to be powered on 30 minutes prior to operation for compliance to the specification (accuracy). *2:Accuracy per temperature change of 1 Example: Accuracy when temperature changes from 25 to 30 0.1% (Reference accuracy) + 0.008%/ (temperature coefficient) (temperature change difference) = 0.14%...
  • Page 12: Part Names

    3. Part Names This section explains the names of the components for the Q66DA-G. Module fixing screw Module fixing bracket External device connector Connector Connector terminal terminal number number Table 3.2 Signal layout Table 3.1 Names of Part Name Description...
  • Page 13: Handling Precautions

    4. Handling Precautions (1) Do not drop the module case or subject it to heavy impact. (2) Do not remove the PCB of the module from its case. Doing so may cause the module failure. (3) Be careful not to let foreign matters such as sawdust or wire chips get inside the module.
  • Page 14: Mounting Module Fixing Bracket

    4.1 Mounting module fixing bracket Hold the Q66DA-G with module fixing bracket after the Q66DA-G is mounted to the base unit. POINT Make sure that the module fixing bracket is hooked on the 3rd slit viewed from the front of Q66DA-G.
  • Page 15: Wiring

    This may increase the effects of noise, surges and induction. (3) Perform a one-point grounding for shielded lines and the shields of shielded cables. (4) When the wiring of the module mounted right to the Q66DA-G is difficult, perform wiring after removing the Q66DA-G.
  • Page 16: External Wiring

    *2:If there is noise or ripples in the external wiring, connect a 0.1 to 0.47 F25V capacitor between the V+/I+ terminal and COM. IMPORTANT Q66DA-G needs to be powered on 30 minutes prior to operation for compliance to the specification (accuracy).Therefore, power on 30 minutes prior to offset/gain setting or after online module replacement.
  • Page 17: Intelligent Function Module Switch Setting

    5.3 Intelligent Function Module Switch Setting The settings for the intelligent function module are performed using the I/O assignment settings of the GX Developer. It can be easy to set by inputting using hexadecimal-4 digits. Table 5.1 Switch setting item for intelligent function module Switch No.
  • Page 18: External Dimensions

    6. External Dimensions FG terminal screw (M3 screw) 89 (3.50) (0.91) 97.5 (3.84) 47 (1.85) 130 (5.12) 27.4 (1.08) 177 (6.97) FG terminal L-Shaped metal fitting FG terminal screw (M3 screw) Unit: mm (inch)
  • Page 19 MEMO...
  • Page 20 6F No.105 Wu-Kung 3rd.Rd, Wu-Ku Branch Hsiang, Taipei Hsine, Taiwan Gothaer Strasse 8 D-40880 Ratingen, Tel : +886-2-2299-2499 GERMANY Korea Mitsubishi Electric Automation Korea Co., Ltd. Tel : +49-2102-486-0 1480-6, Gayang-dong, Gangseo-ku Mitsubishi Electric Europe B.V. UK Seoul 157-200, Korea Branch Tel : +82-2-3660-9552 Travellers Lane, Hatfield, Hertfordshire.,...

Table of Contents