5 DATA USED FOR POSITIONING CONTROL
Pr.24 Manual pulse generator input selection
Set the manual pulse generator input pulse mode. (Only the value specified
against the axis 1 is valid.)
0: A-phase/B-phase; multiplied by 4
1: A-phase/B-phase; multiplied by 2
2: A-phase/B-phase; multiplied by 1
3: PLS/SIGN
Pr.81 Speed-position function selection
Select the mode of speed-position switching control.
0: INC mode
2: ABS mode
Note1: If the setting is other than 0 and 2, operation is performed in the INC mode
with the setting regarded as 0.
Pr.82 Forced stop valid/invalid selection
Set the forced stop valid/invalid. (Only the value specified against the axis 1 is
valid.)
All axis of the servo amplifier are made to batch forced stop when the forced stop
input signal is turned on.
But "Servo READY signal OFF during operation" (error code: 102) does not occur
even if the forced input signal is turned on the during operation.
0: Valid
(Forced stop is used)
1: Invalid (Forced stop is not used)
Note1: If the setting is other than 0 and 1, "Forced stop valid/invalid setting error"
(error code: 937) occurs.
Note2: The "
Md.50
Forced stop input" is stored "1" by setting "Forced stop
valid/invalid selection" to invalid.
5 - 37