12 CONTROL SUB FUNCTIONS
(a) Set the movement range of section A as follows.
(b) Set the movement range of section B as follows.
[7] Setting when the control unit is "degree"
Current value address
The "
Current feed value" address is a ring address between 0 and
Md.20
359.99999 ° .
Fig. 12.16 Current value address when the control unit is "degree".
Setting the software stroke limit
The upper limit value/lower limit value of the software stroke limit is a value
between 0 and 359.99999 ° .
(1) Setting when the software stroke limit is to be validated.
When the software stroke limit is to be validated, set the upper limit value in a
clockwise direction from the lower limit value.
Lower limit
315
Section B
Software stroke limit lower limit value ................ 315.00000
Software stroke limit upper limit value................ 90.00000
Software stroke limit lower limit value ................ 90.00000
Software stroke limit upper limit value................ 315.00000
Fig. 12.17 Software stroke limit when the control unit is "degree"
359.99999°
359.99999°
Set in a clockwise direction
Section A
Upper limit
90
12 - 34
MELSEC-Q
°
°
°
°