15 TROUBLESHOOTING
Related buffer memory
address
Axis 1 Axis 2 Axis 3 Axis 4
32
182
332
482
1518
1618
1718
1818
1519
1619
1719
1819
1517 1617 1717 1817
Refer to Section 5.4
"List of block start data"
Refer to Section 5.5
"List of condition data"
1540 1640 1740 1840 Axis 1 start data No.
1541 1641 1741 1841 Axis 2 start data No.
1542 1642 1742 1842 Axis 3 start data No.
1543 1643 1743 1843 Axis 4 start data No.
1500 1600 1700 1800
Refer to Section 5.3
"List of positioning data"
Set range
(Setting with PLC program)
<External input signal selection>
0,1
<JOG speed>
1 to 50000000 [PLS/s]
1 to 2000000000 [mm/min or others]
<Inching movement amount>
0 to 65535
<Condition data No.>
1 to 10
<Condition operators>
Axis designation:
10
, 20
, 30
, 40
H
H
H
H
60
, 70
, 80
, 90
H
H
H
H
B0
, C0
, D0
, E0
H
H
H
Simultaneous
start axis start
data No.
0 to 600
<Positioning start No.>
1 to 600,
7000 to 7004,
9001 to 9004
<JUMP destination>
1 to 600
<Command speed>
1 to 50000000 [PLS/s]
1 to 2000000000 [mm/min or others]
When the count method 1) or 2) – machine home
position return (OPR) is used, the near-point dog is set
to "0: External input signal of QD75MH". (Refer to
Section 5.2.3 Pr.80 )
Bring JOG speed into the setting range.
(Refer to Section 11.2)
Reduce the inching movement amount.
(Refer to Section 11.3)
Review the condition data No.
(Refer to Section 5.4
Review the simultaneous start axis start data No. .
, 50
,
H
(Refer to Section 5.5
, A0
,
H
H
Review the simultaneous start axis start data No. to
correct value.
(Refer to Section 10.5)
Review the positioning start No., positioning start data
(in block start), and positioning data (in JUMP
instruction) to correct value.
Review the positioning data to correct value.
15 - 11
MELSEC-Q
Remedy
)
Da.14
Da.16
)