12 CONTROL SUB FUNCTIONS
Setting item
Deceleration start
.41
Cd
flag valid
Refer to Section 5.7 "List of control data" for details on the setting details.
Monitor item
Deceleration start
.48
Md
flag
Refer to Section 5.6 "List of monitor data" for information on the storage details.
[3] Deceleration start flag function setting method
To use the "deceleration start flag function", set "1" to the following control data
using a PLC program.
The set data is made valid on the rising edge (OFF to ON) of the PLC READY
signal [Y0].
Setting
value
Set whether the deceleration start flag function
is made valid or invalid.
0: Deceleration start flag invalid
1: Deceleration start flag valid
[4] Checking of deceleration start flag
The "deceleration start flag" is stored into the following buffer memory addresses.
Monitor
value
0: Status other than below
1: Status from deceleration start to next
Setting details
Storage details
operation start or manual pulse generator
operation enable
12 - 97
MELSEC-Q
Buffer memory address
1905
Buffer memory address
Axis
Axis
Axis
Axis
1
2
3
4
899 999 1099 1199