P0400 – Motor Rated Voltage
Adjustable
0 to 690 V
Range:
Proprieties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Set it according to the motor nameplate data and to the motor cable wiring in the connection box.
This value cannot be higher than the rated voltage adjusted in P0296 (Line Rated Voltage).
Note!
In order to validate a new P0400 setting out of the Oriented Start-up Routine it is necessary to
cycle the power of the inverter.
P0401 – Motor Rated current
Adjustable
0 to 1.3xI
Range:
Proprieties:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Set it according to the used motor nameplate data, taking into consideration the motor voltage.
In the Guided Start-up routine the value adjusted in P0401 automatically modifies the parameters related to the
motor overload protection, according to the table 11.2.
P0402 – Motor Rated Speed
Adjustable
0 to 18000 rpm
Range:
CFG
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
Set it according to the used motor nameplate data.
For V/f and VVW controls the setting is from 0 to 18000 rpm.
For vector control the setting is from 0 to 7200 rpm.
43 Motor Data
nom-ND
43 Motor Data
43 Motor Data
Vector Control
Factory
220 V (P0296=0)
Setting:
440 V (P0296=1, 2, 3 or 4)
575 V (P0296=5 or 6)
690 V (P0296=7 or 8)
Factory
Setting:
Factory
Setting:
1.0xI
nom-ND
1750 rpm
(1458 rpm)
11
11-11