Dc Link Regulator [96] - WEG CFW-11 Programming Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Vector Control
Description:
Torque current limitation in function of the speed:
This function stays inactive when the contents of P0171/P0172 are higher or equal to the contents of P0169/
P0170.
P0171 and P0172 do also act during optimal braking limiting the maximum output current.
P0173 – Maximum torque curve type
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
It defines how the actuation of the torque limitation curve will be at the field weakening region. Refer to the figure
11.5.

11.8.7 Dc Link Regulator [96]

For the deceleration of high inertia loads with short deceleration times, the CFW-11 has available the DC Link
Regulation function, which avoids the tripping of the inverter by overvoltage in the DC link (F022).
P0184 – Dc Link Regulation Mode
Adjustable
Range:
11
Proprieties:
Access groups
via HMI:
11-28
Torque current limitation
P0170/P0169
P0172/P0171
Synchronous speed
Figure 11.5 - Torque limitation actuation curve at maximum speed
0 = Ramp
1 = Step
Vector
01 PARAMETER GROUPS
29 Vector Control
95 Torque Curr.Limit
0 = With losses
1 = Without losses
2 = Enable/Disable DIx
CFG and Vector
01 PARAMETER GROUPS
29 Vector Control
96 DC Link Regulator
P0173 = 0
P0173 = 1
P0134
P0190
x
P0400
n
Factory
0
Setting:
Factory
1
Setting: